50 / 74
00U07352250-A_ EN
AHP60
26/32 kW -
Installation, Use and Maintenance
It normally displays the water outlet temperature in tenths of a degree Celsius or the alarm code
is displayed if there is at least one alarm in progress. If several alarms are in progress, the first
one is displayed, while the second one is displayed after the first one has been reset.
Menu
Below is a description of the main navigation functions in the menus, also explaining some
functions that are harder to understand. The main menu also managed the following sections:
MENU
LABEL
PASSWORD LEVEL
OTHER CONDITIONS
Setpoint *
Set
User
Manual operation without Ecomod Heat Pump
Control
Sensor
tP
Installer
---
Alarms
Err
User
Only if errors in progress
Digital inputs
Id
Installer
---
Parameters
Par
Installer
---
Password
PSS
User
---
Hours of operation
oHr
Installer
---
USB
USb
Installer
Only if a USB stick is present, see “software”
instructions
Firmware version
Fir
Installer
---
Error history
Hist
Installer
Only if there is data in the history
Access the PSS menu to enter the maintenance technician password “195” and to activate
access to a higher level. Once all of the menus have been quit, the password privileges are lost
and the password needs to be entered once again.
5.2. “Set” setpoint menu
(For manual operation only)
SETPOINT
DESCRIPTION
UNIT BY DEFAULT
RANGE
Coo
- not used -
--
--
--
Hea
Setpoint in manual operation without Ecomod Heat
Pump Control connected. (Manual mode)
°C
45.0
25 ÷ 60
Coo2
- not used -
--
--
--
Hea2
- not used -
--
--
--
The different setpoints can be displayed and modified. This menu is not used automatically with
Ecomod Heat Pump Control.
Note:
To operate manually without connection to the Ecomod Heat Pump Control, the
pairing between the 2 must be cancelled:
Power down the Ecomod Heat Pump Control or disconnect the communication bus
between the 2, then switch off the heat pump for a few seconds via the proximity switch,
then restart it