12 Status and Operating Information
Operate the XS/SC26-2 Safety Controller using either the onboard interface or Software to monitor ongoing status.
Operate the SC10-2 Safety Controller using the Software to monitor ongoing status.
12.1
XS/SC26-2
LED Status
LED
Status
Meaning
All
Off
Initialization Mode
Sequence:
Green On for 0.5 s
Red On for 0.5 s
Off for 0.5 s minimum
Power applied
Power/Fault
Off
Power Off
Green: Solid
Run mode
Green: Flashing
Configuration or Manual Power-Up mode
Red: Flashing
Non-operating Lockout condition
Red: Fast Flashing
Safety Bus Communication Issue
USB
(Base Controller)
Off
No link to the PC established
Green: Solid
Link to the PC established
Green: Flashing for 5 s
XM configuration match
Red: Flashing for 5 s
XM configuration mismatch
Inputs
Green: Solid
No input faults
Red: Flashing
One or more inputs is in the Lockout condition
SO1, SO2
Off
Output not configured
Green: Solid
Safety Output On
Red: Solid
Safety Output Off
Red: Flashing
Safety Output fault detected or EDM fault detected or AVM fault detected
LED Status for Split Outputs
Meaning
Green: Solid
Both outputs are On
Red: Solid
SO1 and/or SO2 Off
Red: Flashing
SO1 and/or SO2 fault detected
Ethernet Diagnostic LEDs
Amber LED
Green LED
Description
On
Varies with traffic
Link established/normal operation
Off
Off
Hardware failure
Amber LED and Green LED Flash in Unison
Description
5 flashes followed by several rapid flashes
Normal power up
1 flash every 3 seconds
Contact Banner Engineering
2 flash repeating sequence
In the past 60 seconds, a cable was unplugged while active
3 flash repeating sequence
A cable is unplugged
XS/SC26-2 and SC10-2 Safety Controllers
132