Device description
Variant with 1x CAN bus and 1x RS232
LED
Color
Status
Description
Interface
OPS1
-
-
Reserved.
-
OPS2
Yellow
On
TxD/RxD: Data is being transmitted or received.
Off
Terminating resistor not switched on.
OPS3
Yellow
On
Terminating resistor switched on.
IF7: CAN bus
OPS4
Yellow
On
TxD/RxD: Data is being transmitted or received.
IF9: RS232
OPS5
-
-
Reserved
-
Variant with 1x CAN bus and 1x RS485
LED
Color
Status
Description
Interface
OPS1
-
-
Reserved.
-
OPS2
Yellow
On
TxD/RxD: Data is being transmitted or received.
Off
Terminating resistor not switched on.
OPS3
Yellow
On
Terminating resistor switched on.
IF7: CAN bus
OPS4
Yellow
On
TxD/RxD: Data is being transmitted or received.
Off
Terminating resistor not switched on.
OPS5
Yellow
On
Terminating resistor switched on.
IF10: RS485
4.7.6 Fieldbus interfaces
Pinout
Figure
Terminal
Description
X2X Link
1
X2X
X2X data
2
SHLD
Shield
3
X2X\
X2X data inverted
4
X2X⊥
X2X ground
CAN bus
5
CAN_H
CAN High
6
CAN_L
CAN Low
7
GND
Ground
CAN bus
8
GND
Ground
9
CAN_L
CAN Low
10
CAN_H
CAN High
RS232
8
GND
Ground
9
RxD
Receive signal
10
TxD
Transmit signal
RS485
8
GND
Ground
9
DATA\
Data inverted
10
DATA
Data
Required accessories
0TB5104.2110-01
Accessory terminal block, 10-pin (3.5), cage clamp terminal block, 1.5 mm²
Interface
Maximum transfer length
X2X Link
100 m between 2 nodes (segment length)
Bus length up to 25 m: 1 Mbit/s
Bus length up to 60 m: 500 kbit/s
Bus length up to 200 m: 250 kbit/s
CAN
Bus length up to 1000 m: 50 kbit/s
RS232
115.2 kbit/s
RS485
115.2 kbit/s
4.7.7 Reset button
The device is set to mode SERVICE mode with the reset button by default. This setting can be changed in Au-
tomation Studio.
32
Power Panel C80 User's manual V1.02