Installation and wiring
5.7 Securing the connecting cables
Display size 15.6"
On Power Panel variants with 15.6" display size, cables
can be relieved of tensile stress using the cable clamps
provided on the back of the device.
Display size 12.1" and smaller
For display sizes between 5.7" and 12.1", accessories
for installing and protecting the attachment cables from
tensile stress are included in delivery.
Required accessories from the content of delivery:
•
2x M3x5 screws (max. tightening torque 0.55
Nm)
•
Accessory plate for securing the cables
1. Attach the accessory plate (1) to the back of the
device.
2. Secure the accessory plate with the mounting
screws (2).
✓
The attachment cables can now be secured to the
accessory plate using cable ties.
Securing the cables to the grounding plate
1)
Ground conductor
The connection to ground potential must be as short as possible and sufficiently strong (≥4 mm²) over the
intended blade terminal (Faston 6.3 mm).
2)
Unshielded cables
All unshielded cables must be relieved of tensile stress at the grounding plate using cable ties.
3)
Shielded cables
A central ground connection is available to effectively deflect interference. All cable shields must be con-
nected to the grounding plate with good conductivity using cable ties or by other means.
2
1
3
Figure 4: (symbolic image)
Power Panel C80 User's manual V1.02