Device description
4.6.2 Temperature sensor positions
B
A
ADI sensors
Position Measuring
point for
Measurement
Max. specified [°C]
System unit sensor 1
A
CPU/RAM
Temperature of the processor area
4PPC80.0573-xxx:
90
4PPC80.0702-xxx:
95
4PPC80.101E-xxx:
90
4PPC80.121E-xxx:
90
4PPC80.156B-xxx:
85
System unit sensor 2
B
Fieldbuses
Temperature of the fieldbus 1 area
4PPC80.0573-xxx:
95
4PPC80.0702-xxx:
95
4PPC80.101E-xxx:
90
4PPC80.121E-xxx:
90
4PPC80.156B-xxx:
90
4.6.3 Derating the ambient temperature
If the device is installed outside the corresponding specifications, derating the maximum permissible ambient tem-
perature must be taken into account (see
"Ambient conditions" on page 14
). Depending on the display size, der-
ating must be taken into account under the following conditions:
•
Spacing for air circulation is not observed (see
).
•
Permissible mounting orientations are not observed (see
"Mounting orientations" on page 41
The following derating must be taken into account during commissioning:
Display size
Condition for derating
5.7"
7.0"
10.1"
12.1"
15.6"
Spacing for air circulation not observed
10°C
10°C
10°C
10°C
10°C
Deviation from permissible mounting orientations
(e.g. horizontal)
5°C
1)
5°C
1)
-
-
-
Installation cutout: Wall thickness >4 mm
5°C
5°C
5°C
5°C
5°C
High display brightness
-
-
-
-
-
Max. derating (all conditions apply)
20°C
20°C
15°C
15°C
15°C
1)
With horizontal mounting orientation
If one or more of the above conditions apply, the device is permitted to be derated up to the maximum operating
temperature (see ambient conditions in the technical data) minus the specified derating temperatures.
If several conditions apply, the individual derating values must be added together.