Installation and wiring
5.3 Installing with retaining clips
Figure: Retaining clips (symbolic)
The retaining clips are designed for a certain thickness of the material
to be clamped (max. 6 mm, min. 2 mm).
A large flat-blade screwdriver is needed to tighten and loosen the screw.
The device must be installed on a flat, clean and burr-free surface since
tightening screws on an uneven area can result in damage to the display
or the ingress of dust and water.
See also:
"Requirements for the installation cutout" on page 37
.
Procedure
1. Insert the device into the front of the prepared, burr-free and flat installation cutout. For the dimensions of the
installation cutout, see section "Dimensions" for the individual devices.
2. Install the retaining clips on the device. To do this, insert the clips into the openings on the sides of the device
(indicated by the orange circles). The number of openings may vary depending on the size of the device.
Figure: Using the retaining clips
3. Slide the retaining clips all the way to the back of the openings.
Figure: Sliding the retaining clips back
4. Secure the retaining clips to the wall or control cabinet panel by tightening the mounting screws with a flat-
blade screwdriver.
Figure: Securing the retaining clips
Torque limiting is built into the retaining clips.
Power Panel C80 User's manual V1.02
39