Device description
4.6 Environmental properties
4.6.1 Spacing for air circulation
To ensure sufficient air circulation, a specified clearance must be provided above, below, to the side and behind
the device. For the minimum specified clearance, see the following diagrams. This is valid for all variants.
Information:
The following figure and table exclusively show the thermal view of the complete system. If additional
space is required for operating or servicing the device, this must be taken into account during instal-
lation.
The air inlet and air outlet are shown in the following figure.
Legend
1)
Air outlet
2)
Air inlet
Name
Minimum spacing [mm]
Name
Minimum spacing [mm]
S1
≥ 20
S2
≥ 100
S3
≥ 50
-
Caution!
The specified spacing for air circulation applies at the maximum specified ambient temperature. The
maximum specified ambient temperature is not permitted to be exceeded!
If the specified spacing for air circulation cannot be maintained, the maximum specified temperatures
of the temperature sensors (see
"Temperature sensor positions" on page 28
) must be monitored in
the application and appropriate measures taken if these values are exceeded.
Power Panel C80 User's manual V1.02
27