Automation PC 620 User's Manual V 1.90
7.1 Ground resistance
7.2 Insulation resistance
Test carried out according to
EN 61131-2
Limits according to
EN 60204-1
1)
1) See EN 60204-1:1997 page 62, table 9.
Limits according to
EN 61131-2
Ground resistance: housing (from
any metal part to the ground
terminal)
Smallest effective cross section of
the protective ground conductor
for the branch being tested
Maximum measured voltage drop
at a test current of 10 A
Test current 30 A for 2 min,
<
0.1 Ohm
1.0 mm²
3.3 V
1.5 mm²
2.6 V
2.5 mm²
1.9 V
4.0 mm²
1.4 V
>
6.0 mm²
1.0 V
Table 276: Test requirements - ground resistance
Test carried out
Limits according to
EN 60204-1
1)
1) See EN 60204-1:1997 page 62, table 9.
Insulation resistance: main circuits
to protective ground conductor
>
1 MOhm at 500 VDC voltage
Table 277: Test requirements - insulation resistance
Содержание Automation PC 620
Страница 2: ...2 Automation PC 620 User s Manual V 1 90...
Страница 4: ...4 Automation PC 620 User s Manual V 1 90...
Страница 6: ...6 Automation PC 620 User s Manual V 1 90...
Страница 204: ...204 Commissioning Connection examples Automation Panel 900 Automation PC 620 User s Manual V 1 90...
Страница 376: ...376 Maintenance servicing International certifications Automation PC 620 User s Manual V 1 90...
Страница 487: ...Appendix A Glossary Appendix A 487 Automation PC 620 User s Manual V 1 90...
Страница 488: ...488 Appendix A Glossary Automation PC 620 User s Manual V 1 90...
Страница 512: ...Index 512 Automation PC 620 User s Manual V 1 90...