28
Functional Description
8 2 5
Passive emergency call function
("Passive emergency")
The passive emergency call function is used to summon help
if the person involved in an accident is no longer capable of
triggering an active emergency call. This function is only useful
if people located in the vicinity can be alerted via a connected
loud horn or if an emergency call TD is installed to alert other
assistance-providing persons. All active commands are ended
and no other commands accepted (command lock).
The passive "Emergency call trigger" is set off automatically and
involuntarily if:
The transmitter has not been operated over a given period
of time (factory setting: 180 s) and the receiver has not
received anymore commands
(range monitoring)
The transmitter is not moved anymore (factory setting:
180 s)
(acceleration monitoring)
The transmitter is tilted at a particular angle (factory set-
ting: greater than 45°, 180 s)
(position monitoring)
The function "Passive emergency" is switched off on delivery
(factory settings). You must switch on this function if it is requi-
red (see operations / passive emergency).
The "Siren" output is not monitored upon delivery
(factory setting); but it can be parameterized to be
monitored.
2
s
2
s
1
s
1
s
120 s
180 s
Com-
mands
Siren
Main alarm
Pre-alarm
With canceling
the passive
emergency-
criterion
With O + I
(switch off/on)
"Emergency"
output
Reset
alarms
Passive emergency
criterion
Passive emergency sequence
Passive emergency is triggered by one of the passive emer-
gency criteria: Acceleration monitoring or range monitoring
or position monitoring
First the pre-alarm (2 s sound, 2 s pause) and after 120 s
Main alarm (1 s sound, 1 s pause) through the siren
Already activated commands (e.g. pull drum) are switched
off, other dangerous commands are blocked.
On expiry of the pre-alarm time, the "Emergency" output is
switched (e. g. for activating an emergency-call transmission
device).