7-14 Parameter Descriptions
MN761
7.3 Function Group2
Continued
Parameter #
Access
Parameter Name, Value Range, Description and Preset Value
RW
Load Inertia Rate
(Range:
0- Load inertia rate is less than 10 times that of motor inertia
1- Load inertia rate is approximately 10 times the motor inertia.
2- Load inertia rate is more than 10 times that of motor inertia.)
Sets the load inertia rate.
Preset Value:
0
RW
PWM Frequency
(Range: 1-15kHz)
Sets the PWM for the PWM output.
Preset Value:
3
RW
Control Mode
(Range:
0- Volts/Frequency
1- Slip Compensation
2- PID Feedback
3- Sensorless Vector )
Sets the control mode for the drive
Preset Value:
0
RW
Auto Tuning
(Range:
0- Off. Auto tune will not.
1- On. Parameters H42 and H44 are automatically measured and adjusted.
Specifies whether or not H42 and H44 will be measured automatically.
Preset Value:
0
RW
Stator Resistance
(Range: 0-14ohms)
Sets the stator resistance value of the motor. If H41=1 this value is
measured and automatically adjusted.
Preset Value:
CALC
RW
Leakage Inductance
(Range: 0-300.0mH)
Sets the leakage inductance value of the stator and rotor of the motor.
If H41=1 this value is measured and automatically adjusted.
Preset Value:
RW
Sensorless P Gain
(Range: 0-32767)
Sets the P Gain for Sensorless Vector Control of the motor.
Preset Value:
1000
Parameter is only displayed when H40=2 or 3.
RW
Sensorless I Gain
(Range: 0-32767)
Set the I Gain for the motor during Sensorless Vector Control.
Preset Value:
100
Parameter is only displayed when H40=2 or 3.
RW
PID Feedback
(Range:
0- Terminal I Input (0-20 mA)
1- Terminal V1 Input (0-10V))
Sets the feedback type of PID controller.
Preset Value:
0
Parameter is only displayed when H40=2 or 3.
Содержание VS1SM
Страница 1: ...Installation Operating Manual VS1SM Single Phase AC Drive 10 07 MN761...
Страница 10: ...2 2 General Information and Ratings MN761...
Страница 28: ...6 8 Using the Keypad MN761...
Страница 57: ...MN761 Customizing for Your Application 8 1 Chapter 8 Customizing for Your Application...
Страница 58: ...8 2 Customizing for Your Application MN761...
Страница 63: ...MN761 Parameter Tables B 1 Appendix B Parameter Tables Refer to Chapter 7...
Страница 64: ...B 2 Parameter Tables MN761 B 1 1 Basic Parameters Continued...
Страница 69: ...Baldor District Offices...
Страница 71: ...Series VS1SM Single Phase AC Control MN761...