MN761
Parameter Descriptions 7-9
7.2 Function Group1
Continued
Parameter #
Access
Parameter Name, Value Range, Description and Preset Value
RW
Stall Prevent
(Range:
0- No stall prevention.
1- During acceleration. Accel is stopped when motor current > F60.
2- During constant run: Motor decels when motor current > F60.
3- During both accel and Constant run.
4- During deceleration. Decel is stopped when link volts > preset.
5- During both accel and decel.
6- During both decel and Constant run.
7- During accel, decel and Constant run.)
Sets when stall prevention is active.
Preset Value:
0
Current
Freq.
F60
t1t2
Digital or Relay
Output
DC link voltage
Freq.
Accel
Decel
Decel
Digital or Relay
Output
Digital or relay output
RW
Stall Prevention Level
(Range: 30-150%)
Sets the motor current level required to activate stall prevention.
Set as a % of H33.
Preset Value:
150