MN761
Parameter Descriptions 7-25
7.4 I/O Group
Continued
Parameter #
Access
Parameter Name, Value Range, Description and Preset Value
RW
Input Terminal Status Display
(Range: N/A)
Displays the On/Off status of each digital input.
Preset Value:
N/A
ON
OF F
P1
P2
P3
P4
P5
Example:
P1, P3, P4 are ON and P2, P5 are OFF.
RW
Output Terminal Status Display
(Range: N/A)
Displays the On/Off status of each digital output.
Preset Value:
N/A
30AC
ON
OF F
Example:
Digital Output MO=On
Relay output 30AC=Off.
MO
RW
Filtering Time Constant for Digital Inputs
(Range: 2-50)
Adjusts the noise immunity of the Inputs. Increased values result in slower
response times.
Preset Value:
15
RW
Preset Speed 4
(Range: 0-400Hz)
Sets Frequency for Preset Speed 4. Can not be greater than F21.
Preset Value:
30.00
RW
Preset Speed 5
(Range: 0-400Hz)
Sets Frequency for Preset Speed 5. Can not be greater than F21.
Preset Value:
25.00
RW
Preset Speed 6
(Range: 0-400Hz)
Sets Frequency for Preset Speed 6. Can not be greater than F21.
Preset Value:
20.00
RW
Preset Speed 7
(Range: 0-400Hz)
Sets Frequency for Preset Speed 7. Can not be greater than F21.
Preset Value:
15.00
RW
Accel Time 1
(Range: 0-6000sec)
Sets the Acceleration time for Preset Speed 1.
Preset Value:
3.0
RW
Decel Time 1
(Range: 0-6000sec)
Sets the Deceleration time for Preset Speed 1.
Preset Value:
3.0
Содержание VS1SM
Страница 1: ...Installation Operating Manual VS1SM Single Phase AC Drive 10 07 MN761...
Страница 10: ...2 2 General Information and Ratings MN761...
Страница 28: ...6 8 Using the Keypad MN761...
Страница 57: ...MN761 Customizing for Your Application 8 1 Chapter 8 Customizing for Your Application...
Страница 58: ...8 2 Customizing for Your Application MN761...
Страница 63: ...MN761 Parameter Tables B 1 Appendix B Parameter Tables Refer to Chapter 7...
Страница 64: ...B 2 Parameter Tables MN761 B 1 1 Basic Parameters Continued...
Страница 69: ...Baldor District Offices...
Страница 71: ...Series VS1SM Single Phase AC Control MN761...