4-2 Power Wiring
MN761
4.2
Power Disconnect
A power disconnect should be installed between the input power service and the drive for a fail safe
method to disconnect power. The drive will remain in a powered‐up condition until all input power is
removed from the drive and the internal bus voltage is depleted.
4.3
Protective Devices
Recommended fuse sizes are based on the following:
115% of maximum continuous current for time delay.
150% of maximum continuous current for Fast or Very Fast action.
Note:
These recommendations do not consider harmonic currents or ambient temperatures greater than
45
°
C.
Be sure a suitable input power protection device is installed. Use the recommended fuses and wire sizes
shown in Table 4‐1 is based on the use of copper conductor wire rated at 75
°
C. The table is specified
for NEMA B motors.
Fast Action Fuses:
240VAC, Buss
®
KTN; 460VAC, Buss
®
KTS
Very Fast Action:
240VAC, Buss
®
JJN; 460VAC, Buss
®
JJS
Semiconductor
240VAC, Ferraz Shawmut A50QS
Buss
®
is a trademark of Cooper Industries, Inc.
4.4
Electrical Installation
All interconnection wires between the drive, AC power source, motor, host control and any operator
interface stations should be in metal conduits or shielded cable must be used. Use listed closed loop
connectors that are of appropriate size for wire gauge being used. Connectors are to be installed using
crimp tool specified by the manufacturer of the connector. Only class 1 wiring should be used.
Table 4‐1 Fuse & Wire Size and Terminal Tightening Torque Specifications
Catalog Number
Input Fuse (Amps)
Wire Gauge
Tightening Torque
Fast Acting (UL)
AWG
mm
2
lb-in
Nm
VS1SM80PF, VS1SM80P5-F
10A
14
2.5
9
4.5
VS1SM81, VS1SM81-F
20A
14
2.5
9
4.5
VS1SM82, VS1SM82-F
30A
12
4.0
15
1.7
VS1SM83, VS1SM83-F
40A
12
4.0
15
1.7
Note: Wire sizes based on 75
°
C copper wire. Fuses based on 45
°
C ambient, max continuous output and no
harmonic current.
4.4.1
Input Power Connections
All cables must be shielded and the shields must be grounded at the enclosure cable entrance.
1.
Connect the line L1, L2 to the Power Terminal Strip, Figure 4‐3.
2.
Connect the motor leads to U, V and W terminals, Figure 4‐2.
3.
Connect motor ground to the ground terminal
located in the opening at the rear of the drive by
the fan (see Figure 3‐2 for location).
Содержание VS1SM
Страница 1: ...Installation Operating Manual VS1SM Single Phase AC Drive 10 07 MN761...
Страница 10: ...2 2 General Information and Ratings MN761...
Страница 28: ...6 8 Using the Keypad MN761...
Страница 57: ...MN761 Customizing for Your Application 8 1 Chapter 8 Customizing for Your Application...
Страница 58: ...8 2 Customizing for Your Application MN761...
Страница 63: ...MN761 Parameter Tables B 1 Appendix B Parameter Tables Refer to Chapter 7...
Страница 64: ...B 2 Parameter Tables MN761 B 1 1 Basic Parameters Continued...
Страница 69: ...Baldor District Offices...
Страница 71: ...Series VS1SM Single Phase AC Control MN761...