7-10 Parameter Descriptions
MN761
7.3
Function Group2
Parameter #
Access
Parameter Name, Value Range, Description and Preset Value
RW
Jump Code
(Range: 1-95)
Sets the parameter number to jump to within Function Group2.
Allows quick access to a desired parameter.
Preset Value:
1
RO
Fault History 1
(Range: N/A)
Fault information for frequency, current and accel/decel at the fault time.
When a fault occurs during operation, it can be viewed with nOn in the
Drive Group. When the fault is reset it is moved to H1. Fault information
stored in H1 is moved to H2, H2 info is moved to H3 etc. H5 has the
oldest fault information.
Preset Value:
N/A
RW
Fault History 2
(Range: N/A)
See H1.
Preset Value:
N/A
RW
Fault History 3
(Range: N/A)
See H1.
Preset Value:
N/A
RW
Fault History 4
(Range: N/A)
See H1.
Preset Value:
N/A
RW
Fault History 5
(Range: N/A)
See H1.
Preset Value:
N/A
RW
Reset Fault History
(Range: 0-1)
1- Clears H1, H2, H3, H4 and H5 fault history locations.
Preset Value:
0
RW
Dwell Speed
(Range: F23 to 400Hz)
When a run command is issued, dwell frequency is applied to the motor for
H8 time. Then normal accel to speed setpoint will occur.
H8 must be set to a value between F21 and F23.
Preset Value:
5.00
RW
Dwell Time
(Range: 0-10sec)
Sets the duration of the dwell operation (0.0=no dwell operation).
Preset Value:
0.0
RW
Skip Frequency
(Range: 0=Off, 1=On)
Sets whether or not certain frequencies will be skipped to help prevent
undesirable resonance and vibration on the structure of the machine.
Preset Value:
0
RW
Skip Frequency Low Limit 1
(Range: 0-400Hz)
Sets the lower limit of frequency range 1 to skip.
Preset Value:
10.00
Parameter is only displayed when H10=1.
Содержание VS1SM
Страница 1: ...Installation Operating Manual VS1SM Single Phase AC Drive 10 07 MN761...
Страница 10: ...2 2 General Information and Ratings MN761...
Страница 28: ...6 8 Using the Keypad MN761...
Страница 57: ...MN761 Customizing for Your Application 8 1 Chapter 8 Customizing for Your Application...
Страница 58: ...8 2 Customizing for Your Application MN761...
Страница 63: ...MN761 Parameter Tables B 1 Appendix B Parameter Tables Refer to Chapter 7...
Страница 64: ...B 2 Parameter Tables MN761 B 1 1 Basic Parameters Continued...
Страница 69: ...Baldor District Offices...
Страница 71: ...Series VS1SM Single Phase AC Control MN761...