IISAC01 ANALOG CONTROL STATION CONFIGURATION
INTRODUCTION
I-E96-415A
B - 3
Table B-4. IISAC01 Dipswitch S4 Settings
Option
Switch Position
Option Status
1
2
3
4
5
6
7
8
Square
Root
(AI2
only)
1
0
Enable square root
Disable square root
Display
Options
Switch Positions
VAR
SET
OUT
ALPHA
1
2
3
4
5
6
7
8
Normal
Mode
0
0
0
PV
SP
CO
PV,SP,CO
0
0
1
PV
SP
AI1
PV,SP,CO
0
1
0
PV
SP
Blank
PV,SP,CO
0
1
1
PV
SP
All On
PV,SP,CO
1
0
0
AI2
SP
CO
PV,SP,CO
3
1
0
1
AI2
SP
AI1
PV,SP,CO
3
1
1
0
AI2
SP
Blank
PV,SP,CO
3
1
1
1
AI2
SP
All On
PV,SP,CO
3
Bypass
Mode
0
0
0
0
1
Blank
Blank
AI1
DO
2
0
0
0
1
Blank
Blank
DO
DO
0
0
1
0
AI1
Blank
DO
DO
0
0
1
1
DO
Blank
DO
DO
0
1
0
0
DO
Blank
AI1
DO
0
1
0
1
1
AI2
Blank
AI1
DO
2
0
1
1
0
AI2
Blank
DO
DO
0
1
1
1
PV (MFP)
Blank
AI1
DO
1
0
0
0
PV (MFP)
Blank
DO
DO
1
0
0
1
1
AI2
Blank
Blank
DO
NOTES: 0 = CLOSED or ON, 1 = OPEN or OFF.
1. The only display options available when the electric drive option is enabled.
2. The display is blanked when the electric drive option is enabled.
3. The PV displayed is the S1 input to function code 80.