IMRIO02 REMOTE I/O SLAVE MODULE CONFIGURATION
IINTRODUCTION
A - 2
I-E96-415A
®
Table A-2. IMRIO02 Dipswitch S2 (Diagnostic Mode)
Dipswitch Position
Function
1
2
3
4
5
6
7
8
0
0
0
0
0
0
0
0
Remote (RSP) mode
0
1
0
0
0
0
0
0
Local (RMP) mode
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table A-3. IMRIO02 Dipswitch S3 (Communication Cables)
Dipswitch Position
Function
1
2
3
4
5
6
7
8
X
X
X
2
1
0
0
0
Remote (RSP) mode
X
X
X
2
0
1
1
1
Local (RMP) mode
NOTE: 0 = CLOSED or ON
1 = OPEN or OFF.
X = any dipswitch position.
2 = 0 (for electrical cables) or 1 (for fiber optic cables).
Table A-4. IMRIO02 Dipswitch S4 (Communication Cables)
Dipswitch Position
Function
1
2
3
4
5
6
7
8
0
0
0
0
0
0
0
0
Remote (RSP) mode
1
1
1
1
1
1
1
1
Local (RMP) mode
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.