IISAC01 ANALOG CONTROL STATION CONFIGURATION
INTRODUCTION
B - 4
I-E96-415A
®
Table B-5. IISAC01 Jumper JP1, JP2, and JP3 Settings
Jumper
Jumper
Position
Function
JP1
1 - 2
Enable manual override switch
2 - 3
Disable manual override switch
JP2
1
1 - 2
RW type electric drive
2 - 3
Universal type electric drive
JP3
1 - 2
Normal operation
2 - 3
Reserved for factory use only
NOTE:
1. This jumper is labeled JP4 on stations that are revision 6638095A1.
Table B-6. Electric Drive Mode Display Options
Stand-Alone Display
Mode (Dipswitch S3
Positions)
1
Bypass Display Mode
(Dipswitch S4 Positions)
VAR
Bar Graph
OUT
Bar Graph
Action on
Control Output
1
2
3
5
6
7
8
0
0
1
0
0
0
0
Blank
AI1
AI1 to CO
1
1
1
0
0
1
0
1
AI2
AI1
AI1 to CO
1
1
1
1
1
0
0
1
AI2
Blank
AI2 to CO
1
NOTES: 0 = CLOSED or ON, 1 = OPEN or OFF, AI = analog input, CO = control output.
1. Defines the value that will be used as the target CO when the station exits bypass mode and enters normal mode.