IINTRODUCTION
I-E96-415A
A - 1
APPENDIX A - IMRIO02 REMOTE I/O SLAVE
MODULE CONFIGURATION
IINTRODUCTION
Figure
shows the location of the dipswitches used to con-
figure the IMRIO02 module. Tables
through
give the
dipswitch settings to configure the module. This information is
provided as a quick reference guide for personnel installing the
NIRL03 termination module. Configuration consists of setting
the node or slave address (dipswitch S1), diagnostic mode
(dipswitch S2), and type of communication cables used
(dipswitches S3 and S4). Refer to the
IMRIO02 Remote I/O
Slave Module
instruction manual for detailed instructions.
Figure A-1. Remote I/O Slave Module
Table A-1. IMRIO02 Dipswitch S1 (Address Examples)
1
Address
Example
Dipswitch Position
(Binary Value)
1
2
(128)
2
2
(64)
3
(32)
4
(16)
5
(8)
6
(4)
7
(2)
8
(8)
0
0
0
0
0
0
0
0
0
16
0
0
0
1
0
0
0
0
32
0
0
1
0
0
0
0
0
48
0
0
1
1
0
0
0
0
63
0
0
1
1
1
1
1
1
NOTES: 0 = CLOSED or ON, 1 = OPEN or OFF.
1. In remote mode, this dipswitch selects the node address. In local mode, this dipswitch selects the
expander bus address.
2. Dipswitch positions 1 and 2 must remain closed.
T00534A
P1
P3
P2
S1
S3
S4
SLAVE
EXPANDER
SWITCH
DIAGNOSTIC
SWITCH
CABLE TYPE AND
OPERATING MODE
S2
1 2 3 4
OPEN
5 6 7 8
1 2 3 4
OPEN
5 6 7 8
1 2 3 4
OPEN
5 6 7 8
1 2 3 4
OPEN
5 6 7 8
BUS ADDRESS (LOCAL OR RMP MODE)/
NODE ADDRESS (REMOTE OR RSP MODE)