INSTALLATION
SETUP/PHYSICAL INSTALLATION
2 - 8
I-E96-415A
®
NKTU02 AND NKTU12 CABLES
This cable connects the IRL module to an IMRIO02 slave mod-
ule. To install the cable:
1. Pull the IMRIO02 slave module out several inches from the
MMU backplane.
2. If round type cables are already installed in the termination
mounting unit, remove the cable retaining bracket.
3. Insert the J2 end of the NKTU02 or NKTU12 cable into the
MMU backplane slot assigned to the IMRIO02 slave module.
The cable should latch securely into place. Card edge connec-
tor P3 of the slave module connects to this end of the cable.
4. Connect the shield wire extending from the J2 end of the
cable to the shield bus bar.
5. Insert the J1 end of the NKTU01 or NKTU12 cable into the
termination mounting unit backplane slot assigned to the IRL
module. The cable should latch securely into place. Card edge
connector P1 of the IRL module connects to this end of the
cable.
6. Insert the IMRIO02 slave module into the MMU until it
locks into place.
7. Replace or add the cable retaining bracket if round type
cables are installed in the termination mounting unit.
Installing the Termination Module
The IRL module inserts into a standard INFI 90 termination
mounting unit and occupies one slot. To install:
NOTE: Insure all jumpers are configured prior to installation.
1. Verify the slot assignment of the IRL module.
2. Align the IRL module with the guide rails in the termination
mounting unit and partially insert the module.
Terminal Wiring
Station wiring must be connected to the terminal strip. See
Figure
(depending on firmware revision of IRL mod-
ule) for IRL termination module terminal strip assignments.
The station link provides a communication path between an
IMRIO02 slave module and stations. Station link wiring should
be Bailey serial link wire.