IISAC01 ANALOG CONTROL STATION CONFIGURATION
INTRODUCTION
B - 2
I-E96-415A
®
Table B-1. IISAC01 Dipswitch S1 Settings
Option
Switch Position
Option Status
1
2
3
4
5
6
7
8
Diagnostics
1
0
Enable diagnostics (reserved for factory used
only)
Normal operation
Communication
Rate
1
0
Enable 40 kbaud (> 8 stations)
Enable 5 kbaud (< 8 stations)
Station Address
0
1
0
1
0
1
0
1
0
1
0
1
Represents address 0
Represents address 63
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table B-2. IISAC01 Dipswitch S2 Settings
Option
Switch Position
Option Status
1
2
3
Auto Bypass
1
0
Enable auto bypass
Disable auto bypass
Demand Output
1
0
Reverse DO output
Normal DO output
Electric Drive
1
0
Enable electric drive
Disable electric drive
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table B-3. IISAC01 Dipswitch S3 Settings
Display Options
Switch Position
VAR
SET
OUT
ALPHA
1
2
3
Stand Alone Mode
0
0
0
Blank
Blank
Blank
DO
0
0
1
1
Blank
Blank
AI1
DO
3
0
1
0
Blank
Blank
AI1 & DO
2
Blank & DO
0
1
1
AI1
Blank
Blank
DO
1
0
0
Blank
Blank
DO
DO
1
0
1
AI1
Blank
DO
DO
1
1
0
1
AI2
Blank
AI1
DO
3
1
1
1
1
AI2
Blank
DO
3
DO
3
NOTES: 0 = CLOSED or ON, 1 = OPEN or OFF.
1. The only display options available when the electric drive option is enabled.
2. The VAR switch toggles the display from AI1 to DO.
3. The display is blanked when the electric drive option is enabled.