INSTALLATION
UNPACKING AND INSPECTION
2 - 2
I-E96-415A
®
UNPACKING AND INSPECTION
1. Examine the hardware immediately for shipping damage.
2. Notify the nearest Bailey Controls Company sales office of
any such damage.
3. File a claim for any damage with the transportation com-
pany that handled the shipment.
4. Use the original packing material and container to store the
hardware.
5. Store the hardware in an environment of good air quality,
free from temperature and moisture extremes.
SETUP/PHYSICAL INSTALLATION
This section explains how to configure and install the IRL mod-
ule. The required procedures are verification of proper fuse
installation, installing the termination module itself, cable con-
nections, and termination wiring.
Fuse Installation
NIRL03 termination modules with a revision level previous to
R2 contain two, 0.25 inch by 1.25 inch fuses. A one amp/
250 volt fuse (Bailey part number 194776A11001) should be
installed in fuse clip F1. A five amp/250 volt fuse (Bailey part
number 194776A15001) should be installed in fuse clip F2.
NIRL03 termination modules with a revision level of R2 or later
contain two, five millimeter by 20 millimeter fuses. A one amp/
250 volt fuse (Bailey part number 194818A31001) should be
installed in fuse clip F1. A five amp/250 volt fuse (Bailey part
number 194818A35001) should be installed in fuse clip F2.
If the fuses are not installed, insert the fuses into the proper
fuse clip (See Figure
or
for fuse clip locations).
Jumper Configuration
Configure the termination module for the node type and type of
communication cable used by setting jumper J3. Table
shows the possible jumper settings. Figure
illustrates the
difference between middle and end node types.
Cable Connections
The NIRL03 Remote Link Termination Module enables commu-
nication between IMRIO02 modules. Table
lists each cable
and its application. Figure
shows the cables to use and the
cable connections for several different applications of the IRL
module.