INSTALLATION
SETUP/PHYSICAL INSTALLATION
2 - 4
I-E96-415A
®
Table 2-1. Jumper J3 Settings
Jumper
Position
Function
J3
1 - 2
End node type only - coaxial communication cable
2 - 3
Middle node type only - coaxial, twinaxial or serial link wire communication cable
3 - 4
End node type only - twinaxial or serial link wire communication cable
Figure 2-3. Node Positions for NIRL03 Termination Module
Connections
END NODES - TERMINATION RESISTORS NEEDED
(SET J3 ON NIRL03 TO COAX OR TWINAX POSITION)
MIDDLE NODES - TERMINATION RESISTORS
BYPASSED (SET J3 ON NIRL03 TO UNTRM POSITION)
IRL/TRL
IRL/TRL
IRL/TRL
IRL/TRL
T00539A
Table 2-2. NIRL03 Cable Applications
Nomenclature/
Description
Application
Connections
Max
Length
m (ft.)
NKCL01 PVC
communication cable
Connect an IRL module
to another IRL module
The end of one NKTL01 cable to the end
of another NKTYL01cable.
3,000
(10,000)
NKCL02 non-PVC
communication cable
NKPL03 PVC
communication cable
Connects an IRL module
to another IRL module.
Terminal strip of one IRL module to the
terminal strip of another IRL module.
1,371
(4,500)
NKPL04 PVC
communication cable
NKTD02 PVC
termination cable
Connects the IRL module
to a station.
J4 of the IRL module to P1 of the station.
183
(600)
NKTD12 non-PVC
termination cable
NKTL01
communication cable
Connects an IRL module
to an NKCL01/02 cable.
J1 or J2 of the IRL module to one end of
the NKCL01/02 cable.
0.9
(3.0)
NKTU02 PVC
termination cable
Connects the IRL module
to the IMRIO02 slave
module.
P1 of the IRL module to P3 of the
IMRIO02 slave module.
6.1
(20.0)
NKTU12 non-PVC
termination cable