INSTALLATION
SETUP/PHYSICAL INSTALLATION
2 - 10
I-E96-415A
®
2. Feed the station wiring into the terminal strip area and
connect them to the appropriate terminals.
3. Connect an 18 AWG wire from the +24 VDC bus of the ter-
mination mounting unit to the +24 VDC terminal of the IRL
module.
4. Connect an 18 AWG wire from the common bus of the ter-
mination mounting unit to the common terminal of the IRL
module.
5. Insert the IRL module until it locks securely into place.
6. Replace (snap on) the front cover.
The NIRL03 module is ready for operation if:
1. The fuses are installed.
2. The jumpers are configured for the node type and type of
communication cable used.
3. All required cables are installed and verified.
4. Power is connected and applied to the IRL module.