3. Configuration of the Operating Mode and System Parameters
25
© Copyright Reserved Autonics Co., Ltd.
[Home Search Mode configuration]
Item
Configuration value
Note
Near Home Signal Level(nSTOP0) Low
Since the limit signal is used,
the level is same with the limit signal
Home Signal Level(nSTOP1)
Low
Since the limit signal is used,
the level is same with the limit signal
Z Signal Level(nSTOP2)
Low
Not used
Step 1 Enable
Enable
Operation
Step 1 Direction
-
- direction
Step 2 Enable
Enable
Operation
Step 2 Direction
-
- direction
Step 3 Enable
Disable
Not operated
Step 3 Direction
-
Step 4 Enable
Enable
Operation(escaping the limit)
Step 4 Direction
+
+ direction
Position Clear
Enable
Clear position counter after
completing home search
Using Limit Signal
Enable
Use
DCC Enable
Disable
Not used
DCC Level
0
DCC Width(μsec)
10