To remove, push the SIM card firmly into the slot until you hear a click. Releasing will then
cause the SIM card to partially eject, allowing you to easily take out the card.
Guidelines for Installing the STRIDE SiteLink Router
When designing the layout of your system, always separate the devices that generate high voltage
and high electrical noise from the low-voltage, logic-type devices such as the STRIDE SiteLink
router. Also consider the heat-generating devices and locate the electronic-type devices in the
cooler areas of your cabinet. Reducing the exposure to a high-temperature environment will
extend the operating life of the STRIDE SiteLink router.
Consider also the routing of the wiring for the devices in the panel. Avoid placing low-voltage
signal wires and communications cables in the same tray with AC power wiring and high-
energy, rapidly-switched DC wiring.
The STRIDE SiteLink router is designed to be cooled using natural convection. For proper
cooling, you must provide a clearance of at least 25 mm above and below the device. Also, allow
at least 25 mm of depth between the front of the device and the inside of the enclosure.
Wiring
Wiring Guidelines
WARNING: To minimize the risk of potential safety problems, you should follow all applicable local and
national codes that regulate the installation and operation of your equipment. These codes vary from area
to area and it is your responsibility to determine which codes should be followed, and to verify that the
equipment, installation, and operation are in compliance with the latest revision of these codes.
Equipment damage or serious injury to personnel can result from the failure to follow all applicable
codes and standards. We do not guarantee the products described in this publication are suitable for
your particular application, nor do we assume any responsibility for your product design, installation, or
operation.
If you have any questions concerning the installation or operation of this equipment, or if you need
additional information, please call technical support at 1-800-633-0405 or 770-844-4200.
This publication is based on information that was available at the time it was printed. At
Automationdirect.com
®
we constantly strive to improve our products and services, so we reserve the right
to make changes to the products and/or publications at any time without notice and without obligation.
This publication may also discuss features that may not be available in certain revisions of the product.
Proper grounding and wiring of all electrical equipment is important to help ensure the
optimum operation of the SiteLink router and to provide additional electrical noise protection
for your application.
The SiteLink router comes with a female 4-pin plug-in connector with screw connection (type:
Weidmuller BL 5.08/04/180 SN BK BX).
Содержание STRIDE SiteLink SE-SL3011
Страница 1: ...Manual Number SE SLVPN USER M Industrial VPN Router USER MANUAL SiteLink Series...
Страница 2: ......
Страница 6: ......
Страница 8: ......
Страница 14: ...Table of Contents STRIDE SiteLink Series Industrial VPN Routers User Manual 1st Edition vi...
Страница 123: ......