STRIDE
®
SiteLink Series Industrial VPN Routers User Manual
1st Edition
D-8
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Appendix D: Data Logging Address Notation
Reading Holding Registers (Function Code 3)
Function Code SiteLink Modbus Address
Data Type
Do-more! Address**
3
0
INT16, UINT16 or
BOOL*
MHR1
3
1
MHR2
3
65534
MHR65535
3
0
INT32 or UINT32
-
3
1/2
MHRD
3
65533/65534
MHR6553D
3
0
FLOAT32
-
3
1/2
MHRRD
3
65533/65534
MHR6553RD
* BOOL: When using BOOL with Input and Holding Registers, a zero value in the register indicates False in the data logger.
Any non-zero value indicates True in the data logger.
** Double integers (32 bit) can only be used on even number addresses in Do-more! (MIR2, MIR4, etc…).