STRIDE
®
SiteLink Series Industrial VPN Routers User Manual
1st Edition
D-6
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Appendix D: Data Logging Address Notation
Reading Input Registers (Function Code 4)
Function Code SiteLink Modbus Address
Data Type
DirectLogic Address
4
0
INT16, UINT16 or
BOOL*
V0
4
17055
V41237
4
0/1
INT32 or UINT32
V0/V1
4
1/2
V1/V2
4
17054/17055
V41236/V41237
4
0/1
FLOAT32
V0/V1
4
1/2
V1/V2
4
17054/17055
V41236/V41237
* BOOL: When using BOOL with Input and Holding Registers, a zero value in the register indicates False in the data logger.
Any non-zero value indicates True in the data logger.
Reading Holding Registers (Function Code 3)
Function Code SiteLink Modbus Address
Data Type
DirectLogic Address
3
0
INT16, UINT16 or
BOOL*
V0
3
17055
V41237
3
0/1
INT32 or UINT32
V0/V1
3
1/2
V1/V2
3
17054/17055
V41236/V41237
3
0/1
FLOAT32
V0/V1
3
1/2
V1/V2
3
17054/17055
V41236/V41237
* BOOL: When using BOOL with Input and Holding Registers, a zero value in the register indicates False in the data logger.
Any non-zero value indicates True in the data logger.