![AUMA TIGRON TR-M1000X Скачать руководство пользователя страница 68](http://html1.mh-extra.com/html/auma/tigron-tr-m1000x/tigron-tr-m1000x_operation-instructions-manual_3016515068.webp)
Features and functions
Deactivation/activation from remote
Bluetooth module
●
Type of seating: limit or torque seating respectively for end positions OPEN and
CLOSED
●
Torque by-pass
●
Stepping mode
●
Any 8 intermediate positions: can be set between 0 and 100 %, reaction and signal
behaviour programmable
●
Running indication blinking: adjustable
Standard:
Application functions
●
Positioner:
-
Position setpoint via analogue input 0/4 – 20 mA
-
Programmable behaviour on loss of signal
-
Automatic adaptation of dead band (adaptive behaviour selectable)
-
Split range operation
-
MODE input for selecting between OPEN-CLOSE and setpoint control
Options:
●
EMERGENCY operation (behaviour to be selected)
-
Tripping: Digital input: Low active
-
Reaction: Stop, end position CLOSED, end position OPEN, setpoint position
-
Torque monitoring can be by-passed during EMERGENCY operation
Standard:
Safety functions
●
Enabling local controls via digital input "Enable LOCAL": Actuator operation via local
controls can be enabled or disabled
●
Interlock function: Enabling the operation commands OPEN or CLOSE from Remote
via two digital inputs
●
PST (Partial Stroke Test): Programmable to check the function of the actuator
Options:
●
Valve overload protection: Torque limit value adjustable, results in switching off and generates fault
signal
●
Motor temperature monitoring: results in switching off and generates fault signal
●
Monitoring the heater within actuator (if available): generates warning signal
●
Monitoring of permissible operation mode: adjustable, generates warning signal
●
Operation time monitoring: adjustable, generates warning signal
●
Phase failure monitoring: results in switching off and generates fault signal
●
Rotary direction monitoring: results in switching off and generates fault signal
Monitoring function
●
Electronic device ID with order and product data
●
Logging of operating data: A resettable counter and a lifetime counter each for:
-
e.g. motor running time, number of starts, torque switch trippings in end position CLOSED, limit
switch trippings in end position CLOSED, torque switch trippings in end position OPEN, limit
switch trippings in end position OPEN, torque faults CLOSE, torque faults OPEN, motor protection
trippings
●
Time-stamped event report with history for setting, operation and faults
●
Status signals according to NAMUR recommendation NE 107: “Failure", "Function check", "Out of
specification", "Maintenance required"
●
Torque profile:
-
Various reference operations can be executed (e.g. for commissioning)
-
Torque values can be stored as reference profile.
-
Comparison operation can be executed at any time (e.g. for plant control).
-
Tolerance values can be flexibly defined for travel.
-
Values outside the permissible range generate configurable signals to the DCS.
Diagnostic function
TPC T-0A1AAB11-000
Wiring diagram (basic version)
Service conditions
Indoor and outdoor use permissible
Use
Any position
Mounting position
≤
2,000 m above sea level
Installation altitude
>
2 000 m above sea level on request
Refer to name plate
Ambient temperature
Up to 100 % relative humidity across the entire permissible temperature range
Humidity
68
TR-M30X – TR-M1000X
Technical data
TR-MR30X – TR-MR1000X