8.2.1.
Type of seating setting via the device menu
Valve damage due to incorrect setting!
→
The type of seating setting (limit or torque seating) must match the selection for
the valve.
→
Only change the setting with prior consent of the valve manufacturer.
Information
Local actuator settings are made using the Combi-Switch.
●
Operate the yellow shuttle dial
of the Combi-Switch to scroll within the menu
.
●
Operate the black selector switch
(outer ring), either to confirm the selected
menu or to go one step back (ESC).
How to proceed
1.
Open device menu.
Information: If the ID of the indicated page starts with
M, PRM, ...
, you have
already entered the device menu. For further information, refer to:
➭
2.
Select menu
M0086
or
M0087
:
Customer settings M0041
Type of seating M0012
End position CLOSED M0086
End position OPEN M0087
➥
The display shows parameter
PRM0578
or
PRM009
.
Figure 49: For user levels 1–3 (read parameters only):
Information
Use (Enter) to change from user levels 1–3 to a higher user level. For further
information, refer to:
➭
Figure 50: For user levels 4–6 (settings can be changed):
Change settings
3.
Select new value via
. (At least user level 4 required.)
→
Limit
= Limit seating
→
Torque
= Torque seating
Information: The black triangle
▶
shows the saved value. A white triangle
▷
shows the selected value which has not yet been saved.
4.
Save selected value with (Enter)..
➥
The display shortly indicates
Value saved!
. The type of seating is set for the
end position.
5.
Press ESC (Escape) to return for further parameter setting.