Table 20:
Warnings and Out of specification
Remedy
Description/cause
Indication on display
Toggle selector switch in direction
to display the
individual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
Collective signal 06:
Possible cause:
Configuration setting is incorrect.
The device can still be operated with restrictions.
Config. warning
Toggle selector switch in direction
to display the
individual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
Collective signal 15:
Device warnings
The device can still be operated with restrictions.
Internal warning
Check 24 V DC voltage supply.
The external 24 V DC voltage supply of the internal
controls has exceeded the power supply limits.
24 V DC external
●
Check modulating behaviour of actuator.
●
Check parameter
Perm. run time M0356
, re-set
if required.
Warning on time max. running time/h exceeded
Wrn op.mode run time
●
Check modulating behaviour of actuator.
●
Check parameter
Permissible starts M0357
, re-
set if required.
Warning on time max. number of motor starts
(starts) exceeded
Wrn op.mode starts
Check signals:
●
Setpoint E1
●
Actual value E2
●
Actual process value E4
●
For Profibus DP, Profinet, Modbus or Ethernet:
Check connection to master.
●
For Profibus DP or Profinet: Check (clear) status
of master.
The failure behaviour is active since all required
setpoints and actual values are incorrect.
Failure behav. active
Check setpoint signal.
Warning: Loss of signal setpoint position
Possible causes:
For an adjusted setpoint range of e.g. 4 – 20 mA,
the input signal is 0 (signal loss)
For a setpoint range of 0 – 20 mA , monitoring is
not possible.
Wrn setpoint position
The warning indications are automatically cleared
once a new operation command is executed.
●
Check valve.
●
Check parameter
Perm.op. time, manualM0570
.
The set time (parameter
Perm.op. time, manual
M0570
) has been exceeded. The preset operating
time is exceeded for a complete travel from end
position OPEN to end position CLOSED.
Op. time warning
Measure/reduce ambient temperature.
Temperature within actuator controls housing too
high.
Wrn controls temp.
Set time.
Real time clock has not yet been set.
Time not set
Replace button cell.
Voltage of RTC button cell too low.
RTC voltage
Check actuator (PVST settings).
Partial Valve Stroke Test (PVST) could not be suc-
cessfully completed.
PVST fault
Perform RESET or restart PVST.
Partial Valve Stroke Test (PVST) was aborted or
could not be started.
PVST abort
●
Check movement at actuator.
●
Check parameter
Reaction timeM0634
.
No actuator reaction to operation commands within
the set reaction time.
Wrn no reaction
Check/repair FO cables.
Optical receiving signal (channel 1) incorrect (no or
insufficient Rx receive level) or RS-485 format error.
Wrn FOC
1)
Check/repair FO cables.
Warning: FO cable system reserve reached (critical
or permissible Rx receive level)
Wrn FO cable budget
1)
Fit FO cable connection.
Warning FO cable connection is not available.
Wrn FOC connection
1)
Check parameter
Wrn torque OPEN M0768
, re-set
if required.
Limit value for torque warning in direction OPEN
exceeded.
Torque wrn OPEN
59
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X
Corrective action