In selector switch position REMOTE via a digital (I/O interface) with the RESET
command if a digital input is configured for
RESET
signal.
Proof-test motor protection
Test correct function of the motor protection as described hereafter. Perform the
functional test at the latest within the framework of maintenance (refer to chapter
<Servicing and maintenance>).
The test is performed by simulating the motor protection signal via the menu:
Required user level:
Specialist (4)
or higher.
Diagnostics M0022
TMS proof test M1950
Test procedure:
1.
Set selector switch to OFF.
2.
Return to the main menu and select the simulation value in parameter
TMS
proof test M1950
: Select
Thermal test
.
3.
Activate motor protection simulation: Toggle selector switch in direction .
The safety function is correct if no fault signal is displayed.
4.
Reset simulation: Toggle selector switch in direction (exit the simulation
menu) and turn the selector switch to the initial position.
63
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X
Corrective action