![AUMA TIGRON TR-M1000X Скачать руководство пользователя страница 40](http://html1.mh-extra.com/html/auma/tigron-tr-m1000x/tigron-tr-m1000x_operation-instructions-manual_3016515040.webp)
8.
Commissioning
To correctly commission the device, you require the necessary basic knowledge
for menu operation. If you do not have basic knowledge, make sure you famil-
iarise yourself with the basics prior to commissioning.
For further information, refer to:
➭
Commissioning can be made using the Commissioning Assistant or via manual
setting of individual functions.
➭
page 40, Start Commissioning Assistant
➭
page 40, Perform manual commissioning
8.1.
Start Commissioning Assistant
The Commissioning Assistant facilitates commissioning thanks to a structured
navigation through the device menu. Setting the commissioning functions like type
of seating, torque switches and limit switches are easy and intuitive.
Information
Local actuator settings are made using the Combi-Switch.
●
Operate the yellow shuttle dial
of the Combi-Switch to scroll within the menu
.
●
Operate the black selector switch
(outer ring), either to confirm the selected
menu or to go one step back (ESC).
How to proceed
1.
Open device menu.
Information: If the ID of the indicated page starts with
M, PRM, ...
, you have
already entered the device menu. For further information, refer to:
➭
2.
Select menu
Assistant M2236
.
3.
If required, select user level and enter the password. For further information,
refer to:
➭
4.
Select language and confirm with (Enter).
Figure 48:
➥
The assistant is started and the actuator changes to commissioning operation
mode (symbol ).
5.
Follow the instructions issued by the assistant.
8.2.
Perform manual commissioning
For manual commissioning, the following commissioning functions can be individually
checked and set:
1.
Type of seating
➭
page 41, Type of seating setting via the device menu
2.
Torque switching
➭
page 42, Torque seating setting via the device menu
3.
Limit switching
➭
page 43, Limit switching setting via the device menu
40
TR-M30X – TR-M1000X
Commissioning
TR-MR30X – TR-MR1000X