2.
Operate actuator using the yellow shuttle dial
.
➥
The limit switching is correctly set if (standard signalling):
-
the yellow indication light/LED1 is illuminated in end position CLOSED
-
the green indication light/LED5 is illuminated in end position OPEN
-
the indication lights go out after travelling into the opposite direction.
➥
The limit switching is set incorrectly if:
-
the actuator comes to a standstill before reaching the end position
-
one of the red indication lights/LEDs is illuminated (torque fault)
-
the status indication
S0007
in the display signals a fault.
3.
If the end position setting is incorrect: Reset limit switching.
47
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X
Commissioning