![AUMA TIGRON TR-M1000X Скачать руководство пользователя страница 44](http://html1.mh-extra.com/html/auma/tigron-tr-m1000x/tigron-tr-m1000x_operation-instructions-manual_3016515044.webp)
Approach end position
5.
For large strokes, approach the valve end position in motor operation:
5.1 Set selector switch to LOCAL.
5.2 For operation in direction CLOSE: turn yellow shuttle dial in direction .
5.3 For operation in direction OPEN: turn yellow shuttle dial in direction .
Information: To avoid damage, abort operation in time prior to reaching
the end stop (turn shuttle dial to the opposite direction of operation).
5.4 Set selector switch to position OFF.
6.
Engage manual drive and turn handwheel until the valve is closed.
→
When selecting limit seating, turn back the handwheel (by approx. ½ turn
prior to reaching the end position) to allow for potential overrun.
→
For end position CLOSED, continue with step 7 (set end position
CLOSED).
→
For end position OPEN, continue with step 10 (set end position OPEN).
Set end position
CLOSED in the current
position
CMD0009
7.
Use (Enter) to save the current valve position as new “end position CLOSED”.
➥
The display indicates
End pos. CLOSED set!
and the right LED (standard ver-
sion) is illuminated. Now, the end position CLOSED of the limit switching is set.
Figure 54:
8.
If the setting must be corrected: Reset settings with (Enter). The LED goes
out again.
→
Approach “again” the end position (steps 5 + 6) and reset the end position
CLOSED.
9.
If the end position OPEN has been correctly set: Exit the menu with ESC (Es-
cape).
→
Then, proceed with the setting of end position OPEN (step 2).
Set end position OPEN
in the current position
CMD0010
10. Use (Enter) to save the current valve position as new “end position OPEN”.
➥
The display indicates
End pos. OPEN set!
and left LED (standard version) is
illuminated. Now, the end position OPEN of the limit switching is set.
Figure 55:
11. If the setting must be corrected: Reset settings with (Enter). The LED goes
out again.
→
Approach “again” the end position (steps 5 + 6) and reset the end position
OPEN.
12. If the end position OPEN has been correctly set: Exit the menu with ESC (Es-
cape).
→
Then, proceed with the setting of end position CLOSED (step 2).
44
TR-M30X – TR-M1000X
Commissioning
TR-MR30X – TR-MR1000X