![AUMA TIGRON TR-M1000X Скачать руководство пользователя страница 55](http://html1.mh-extra.com/html/auma/tigron-tr-m1000x/tigron-tr-m1000x_operation-instructions-manual_3016515055.webp)
10.2.
Indication lights of local controls
Figure 68: Arrangement and signification of indication lights
End position OPEN reached (blinking: operation in direction OPEN)
Torque fault OPEN
General fault signal, e.g. motor protection tripped
Torque fault CLOSE
End position CLOSED reached (blinking: operation in direction CLOSE)
Bluetooth connection
Indication lights (indications); modify
Different indications can be assigned to LEDs 1 – 5.
Device configuration M0053
Local controls M0159
Indication light 1 (left) M0093
Indication light 2 M0094
Indication light 3 M0095
Indication light 4 M0096
Indicat. light 5 (right) M0097
Signal interm. pos. M0167
Default values (Europe):
Indication light 1 (left)
=
End p. OPEN, blink
Indication light 2
=
End p. CLOSED, blink
Indication light 3
=
Thermal fault
Indication light 4
=
Torque fault OPEN
Indicat. light 5 (right)
=
Torque fault CLOSE
Signal interm. pos.
=
OPEN/CLOSED = Off
Further setting values:
Refer to Manual (Operation and setting).
55
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X
Indications