11.
Signals (output signals)
11.1.
Status signals via output contacts (digital outputs)
Output contacts are used to send status signals (e.g. reaching the end positions,
selector switch position, faults...) as binary signals to the control room.
Status signals only have two states: active or inactive. Active means that the
conditions for the signal are fulfilled.
Information
If equipped with a digital communication interface (fieldbus/Industrial Ethernet/HART),
these signals are only available if an additional parallel interface is available.
11.1.1.
Assignment of outputs
The output contacts (outputs DOUT 1 – 6) can be assigned to various signals.
Required user level:
Specialist (4)
or higher.
Device menu:
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Signal DOUT 1 M0109
Default values:
Signal DOUT 1
=
Fault
Signal DOUT 2
=
End position CLOSED
Signal DOUT 3
=
End position OPEN
Signal DOUT 4
=
Selector sw. REMOTE
Signal DOUT 5
=
Torque fault CLOSE
Signal DOUT 6
=
Torque fault OPEN
11.1.2.
Output coding
The output signals
Coding DOUT 1
–
Coding DOUT 12
can be set either to high
active or low active.
●
High active = output contact closed = signal active
●
Low active = output contact open = signal active
Signal active means that the conditions for the signal are fulfilled.
Required user level:
Specialist (4)
or higher.
Device menu:
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Coding DOUT 1 M0102
Default values:
Coding DOUT 1
=
Low active
Coding DOUT 2
–
Coding DOUT 6
=
High active
11.2.
Analogue signals (analogue outputs)
Valve position
Signal: E2 = 0/4 – 20 mA (galvanically isolated)
Designation in the wiring diagram: AOUT1 (position)
Torque feedback signal
(option)
Signal: E6 = 0/4 – 20 mA (galvanically isolated)
Designation in the wiring diagram: AOUT2 (torque)
Information
If equipped with a digital communication interface (fieldbus/Industrial Ethernet/HART),
these signals are only available if an additional parallel interface is available.
56
TR-M30X – TR-M1000X
Signals (output signals)
TR-MR30X – TR-MR1000X