Figure 24: Profinet connection board with RJ-45 connections
n–1
Profinet cable from previous device
n+1
Profinet cable to next device
(For line topology or redundant ring/MRP - Media Redundancy Protocol)
Profinet connection is made via RJ-45 ports by means of connectors for field
assembly. The scope of delivery includes one RJ-45 Profinet connector for Cat.5
(supplied within electrical connector). Further connectors are available with AUMA
(e.g. for line topology or redundant ring) on request.
Order designations:
●
RJ-45 Profinet connector for Cat.5 (as included in scope of delivery): AUMA
article number K009.706
●
Option: RJ-45 Profinet connector for Cat.6
A
cables: AUMA article number
K009.705
Table 17:
Assignment of RJ-45 Profinet port
Pin
Colour of wire insula-
tion
Function
Signal
1
Yellow
Transmit Data +
TD +
2
Orange
Transmit Data –
TD –
3
White
Receive Data +
RD +
6
Blue
Receive Data –
RD –
Description of LEDs on connection board
Table 18:
Explanation
Status
MODS (Module Status)
No voltage or module in “SETUP” or “NW_INIT”
status
Not Initialised
Red LED: off +
Green LED: off
The module has aborted “NW_INIT” status
Normal Operation
Green LED: illuminated
Diagnostic events available
Diagnostic Events
Green LED: 1 brief pulse
Device in “EXCEPTION” status
Exception Error
Red LED: illum
Red NETS LED: off
Internal device error
Fatal Event
Red LED: illum
Red NETS LED: illuminated
Do not cut power supply!
Firmware update
Green/Red LEDs:
Alternately blinking
26
SA 07.2-UW – SA 16.2-UW / SAR 07.2-UW – SAR 16.2-UW Control unit: electronic (MWG)
Electrical connection
AC 01.2 Non-Intrusive Profinet