5.3.3.
Terminal compartment (for mains connection): close
Figure 20: Close mains terminal compartment
[1]
Connection housing
[2]
Screws for connection housing
[3]
O-ring
[4]
Screws for socket carrier
[5]
Socket carrier
[6]
Cable gland (not included in delivery)
[7]
Blanking plug
Short-circuit due to pinching of cables!
Risk of electric shock and functional failures.
→
Carefully fit socket carrier to avoid pinching the cables.
1.
Insert the socket carrier [5] into the connection housing [1] and fasten with
screws [4].
2.
Clean sealing faces of connection housing [1] and housing.
3.
Check whether O-ring [3] is in good condition, replace if damaged.
4.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
5.
Fit connection housing [1] and fasten screws [2] evenly crosswise.
6.
Fasten cable glands and blanking plugs applying the specified torque to ensure
the required enclosure protection.
23
SA 07.2-UW – SA 16.2-UW / SAR 07.2-UW – SAR 16.2-UW Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Profinet
Electrical connection