9.
Commissioning (basic settings)
1.
Set selector switch to position 0 (OFF).
Information: The selector switch is not a mains switch. When positioned to 0
(OFF), the actuator cannot be operated. The controls' power supply is
maintained.
2.
Switch on the power supply.
Information: Observe heat-up time for ambient temperatures below –30 °C.
3.
Perform basic settings.
9.1.
Type of seating: set
Valve damage due to incorrect setting!
→
The type of seating setting (limit or torque seating) must match the selection for
the valve.
→
Only change the setting with prior consent of the valve manufacturer.
Customer settings M0041
Type of seating M0012
End position CLOSED M0086
End position OPEN M0087
Default value:
Limit
Setting values:
Limit
Seating in end positions via limit switching.
Torque
Seating in end positions via torque switching.
Select main menu
1.
Set selector switch to position 0 (OFF).
2.
Press push button C
Setup
and hold it down for approx. 3 seconds.
➥
Display goes to main menu and indicates:
▶ Display
Select parameter
3.
Select parameter either:
→
click via the menu
to parameter, or
→
via direct display: Press and enter ID
M0086
or
M0087
➥
Display indicates:
End position CLOSED
CLOSE or OPEN
4.
Use
Up ▲ Down ▼
to select:
→
▶ End position CLOSED
→
▶ End position OPEN
➥
The black triangle
▶
indicates the current selection.
5.
Press
Ok
.
➥
Display indicates the current setting:
Limit
or
Torque
➥
The bottom row of the display indicates either:
-
Edit →
continue with step 6
-
Save →
continue with step 10
45
SA 07.2-UW – SA 16.2-UW / SAR 07.2-UW – SAR 16.2-UW Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Profinet
Commissioning (basic settings)