Set end position
CLOSED
CMD0009
(without handwheel)
9.
Set end position CLOSED again :
Information: The following description applies to actuators without handwheel.
For actuators with handwheel, continue with the next step.
9.1 Set selector switch in position Local control (LOCAL) and operate actu-
ator in via push button
(CLOSE) to the end position.
Information: To avoid valve damage, set the torque switching to a value
as low as possible!
9.2 Operate a small distance (in push-to-run operation via push button
(OPEN)) out of end position CLOSED to consider overrun.
9.3 Set selector switch to position 0 (OFF).
➥
Display indicates:
Set end pos.CLOSED? Yes No
Confirm new end posi-
tion
10. Press
Yes
to confirm new end position.
➥
Display indicates:
End pos. CLOSED set!
➥
The left LED is illuminated (standard version) and thus indicates that the end
position CLOSED setting is complete.
11. Make selection:
→
Edit →
back to step 9: Set end position CLOSED "once again"
→
Esc →
back to step 4; either set end position OPEN or exit the menu.
Set end position OPEN
CMD0010
(without hand-
wheel)
12. Re-set end position OPEN:
Information: The following description applies to actuators without handwheel.
For actuators with handwheel, continue with the next step.
12.1 Set selector switch in position Local control (LOCAL) and operate actu-
ator in via push button
(OPEN) to the end position.
Information: To avoid valve damage, set the torque switching to a value
as low as possible!
12.2 Operate a small distance (in push-to-run operation via push button
(CLOSE)) out of end position CLOSED to consider overrun.
12.3 Set selector switch to position 0 (OFF).
➥
Display indicates:
Set end pos. OPEN? Yes No
Confirm new end posi-
tion
13. Press
Yes
to confirm new end position.
➥
Display indicates:
End pos. OPEN set!
➥
The right LED is illuminated (standard version) and thus indicates that the end
position OPEN setting is complete.
14. Make selection:
→
Edit →
back to step 12: Set end position OPEN "once again"
→
Esc →
back to step 4; either set end position CLOSED or exit the menu.
15. After setting the limit switching, reset the torque switching to the value recom-
mended by the valve manufacturer.
Information
If an end position cannot be set: Check the type of control unit in actuator.
49
SA 07.2-UW – SA 16.2-UW / SAR 07.2-UW – SAR 16.2-UW Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Profinet
Commissioning (basic settings)