Warnings and Out of specification
Remedy
Description/cause
Indication on display
Execution of PVST (Partial Valve Stroke Tests) is
required.
PVST required
Maintenance is required.
Maintenance required
Checking and fault remedy are required. Refer to
FQM operation instructions.
FQM fault
FQM fail safe flt
2)
For actuators controls in SIL version
1)
For actuators with fail safe unit
2)
Table 29:
Faults and Failure
Remedy
Description/cause
Indication on display
Drucktaster
Details
drücken, um Einzelmeldun-
gen zu sehen.
For a description of the individual signals, refer to
Manual (Operation and setting).
Collective signal 11:
Configuration error has occurred.
Configuration error
Drucktaster
Details
drücken, um Einzelmeldun-
gen zu sehen.
For a description of the individual signals, refer to
Manual (Operation and setting).
Collective signal 22:
Configuration error has occurred.
Config. error REMOTE
AUMA service
Press push button
Details
to display a list of indi-
vidual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
Collective signal 14:
Internal error has occurred.
Internal error
Perform one of the following measures:
●
Issue operation command in direction OPEN.
●
Set selector switch to position Local control
(LOCAL) and reset fault indication via push
button RESET.
●
Execute reset command via fieldbus.
Torque fault in direction CLOSE
Torque fault CLOSE
Perform one of the following measures:
●
Issue operation command in direction CLOSE.
●
Set selector switch to position Local control
(LOCAL) and reset fault indication via push
button RESET.
●
Execute reset command via fieldbus.
Torque fault in direction OPEN
Torque fault OPEN
Test/connect phases.
●
When connecting to a 3-ph AC system and with
internal 24 V DC supply of the electronics:
Phase 2 is missing.
●
When connecting to a 3-ph or 1-ph AC system
and with external 24 V DC supply of the elec-
tronics: One of the phases L1, L2 or L3 is
missing.
Phase fault
Correct the sequence of the phase conductors L1,
L2 and L3 by exchanging two phases.
The phase conductors L1, L2 and L3 are connected
in the wrong sequence.
Only applicable if connected to a 3-ph AC system.
Incorrect phase seq
●
Check mains voltage.
For 3-phase/1-phase AC current, the permiss-
ible variation of the mains voltage is
±
10 %
(option
±
30 %). The permissible variation of the
mains voltage is
±
5 %
●
Check parameter
Tripping time M0172
, extend
time frame if required.
Due to insufficient mains quality, the controls cannot
detect the phase sequence (sequence of phase
conductors L1, L2 and L3) within the pre-set time
frame provided for monitoring.
Mains quality
54
SA 07.2-UW – SA 16.2-UW / SAR 07.2-UW – SAR 16.2-UW Control unit: electronic (MWG)
Corrective action