5.3.
SF electrical connection (AUMA plug/socket connector)
Figure 16: SF electrical connection
[1]
Cover of actuator controls electrical connection (XK) – (SF version)
For customer connection of power supply and e.g. to control room
[2]
Socket carrier with screw-type terminals
[1]*
Cover of wall bracket plug socket connector (XM) – (S version)
The plug/socket connector of LSW 68 cable set is readily assembled (wired)
For LSW 69 cable set, the plug/socket connector must be opened and the
cables must be connected to the pin carrier.
[2]*
Pin carrier with crimp-type connection
Short description
Plug-in electrical connection with screw-type terminals for power and control contacts.
Control contacts also available as crimp-type connection as an option.
SF version. For power and control cable connection, remove the AUMA plug/socket
connector and the socket carrier from terminal compartment. Removing the cover
is sufficient for connecting the fieldbus cables.
Technical data
Table 13:
Electrical connection via AUMA plug/socket connector
Control contacts
Power contacts
50 pins/sockets
6 (3 equipped) + protective
earth conductor (PE)
No. of contacts max.
1 to 50
U1, V1, W1, U2, V2, W2, PE
Designation
250 V
750 V
Connection voltage max.
16 A
25 A
Rated current max.
Screw connection, crimp-type (option)
Screw connection
Type of customer connection
2.5 mm
2
(flexible or solid)
6 mm
2
(flexible)
10 mm
2
(solid)
Connection diameter max.
20
SA 07.2-UW – SA 16.2-UW / SAR 07.2-UW – SAR 16.2-UW Control unit: electronic (MWG)
Electrical connection
AC 01.2 Non-Intrusive Profinet