Events and registers
The capacitor bank neutral unbalance function (abbreviated "CNU" in event block names) generates
events and registers from the status changes in START, TRIP and BLOCKED. The user can select
which event messages are stored in the main event buffer: ON, OFF, or both. The function offers
one (1) independent stage.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.3.2.2 - 58. Event messages.
Event block name
Event names
CNU1
Alarm Start ON
CNU1
Alarm Start OFF
CNU1
Alarm ON
CNU1
Alarm OFF
CNU1
Start ON
CNU1
Start OFF
CNU1
Trip ON
CNU1
Trip OFF
CNU1
Unbalance detected Bank A ON
CNU1
Unbalance detected Bank A OFF
CNU1
Unbalance detected Bank B ON
CNU1
Unbalance detected Bank B OFF
CNU1
Compensating natural unbalance ON
CNU1
Compensating natural unbalance OFF
The function registers its operation into the last twelve (12) time-stamped registers; this information is
available for all provided instances separately. The register of the function records the ON event
process data for START, TRIP or BLOCKED. The table below presents the structure of the function's
register content.
Table. 5.3.2.2 - 59. Register content.
Date and
time
Event Fault
side Unbalance current
Fuse
operations A
Fuse
operations B
Trip time
remaining
Used SG
dd.mm.yyyy
hh:mm:ss.mss
Event
name
A, B
Measured unbalance
current
Number if
fuses operated
Number of
fuses operated
0...1800 s
Setting group
1...8 active
5.3.2.3 Capacitor bank current unbalance protection (Iuc>; 46C)
The capacitor bank current unbalance protection is used in protecting the capacitor bank with a double
wye configuration. The operating decisions are based on phase current magnitudes which the function
constantly measures. The monitored phase current magnitudes are equal to RMS values. The blocking
signal and the setting group selection control the operating characteristics of the function during
normal operation, i.e. the user or user-defined logic can change function parameters while the function
is running.
The capacitor bank current unbalance function uses a total of eight (8) separate setting groups which
can be selected from one common source.
A
AQ
Q-C255
-C255
Instruction manual
Version: 2.06
74
© Arcteq Relays Ltd
IM00035