Scanning cycle
All digital inputs are scanned in a 5 ms cycle, meaning that the state of an input is updated every 0…5
milliseconds. When an input is used internally in the device (either in group change or logic), it takes
additional 0…5 milliseconds to operate. Theoretically, therefore, it takes 0…10 milliseconds to change
the group when a digital input is used for group control or a similar function. In practice, however, the
delay is between 2…8 milliseconds about 95 % of the time. When a digital input is connected directly
to a digital output (T1…Tx), it takes an additional 5 ms round. Therefore, when a digital input controls a
digital output internally, it takes 0…15 milliseconds in theory and 2…13 milliseconds in practice.
NO
NOTE!
TE!
The mechanical delay of the relay is no
nott included in these approximations!
8.3 Current measurement module
Figure. 8.3 - 185. Module connections with standard and ring lug terminals.
Connector
Description
CTM 1-2
Phase current measurement for phase L1 (A).
CTM 3-4
Phase current measurement for phase L2 (B).
CTM 5-6
Phase current measurement for phase L3 (C).
CTM 7-8
Coarse residual current measurement I01.
CTM 9-10
Fine residual current measurement I02.
A basic current measurement module with five channels includes three-phase current measurement
inputs as well as coarse and fine residual current inputs. The CT module is available with either
standard or ring lug connectors.
The current measurement module is connected to the secondary side of conventional current
transformers (CTs). The nominal current for the phase current inputs is 5 A. The input nominal current
can be scaled for secondary currents of 1…10 A. The secondary currents are calibrated to nominal
currents of 1 A and 5 A, which provide ±0.5 % inaccuracy when the range is 0.005…4 ×
I
n
.
The measurement ranges are as follows:
• Phase currents 25 mA…250 A (RMS)
• Coarse residual current 5 mA…150 A (RMS)
• Fine residual current 1 mA…75 A (RMS)
A
AQ
Q-C255
-C255
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00035
367
Содержание AQ-C255
Страница 1: ...AQ C255 Capacitor bank protection IED Instruction manual ...
Страница 2: ......
Страница 363: ...Figure 7 4 180 Example block scheme A AQ Q C255 C255 Instruction manual Version 2 06 Arcteq Relays Ltd IM00035 361 ...
Страница 384: ...Figure 8 14 202 Device installation A AQ Q C255 C255 Instruction manual Version 2 06 382 Arcteq Relays Ltd IM00035 ...