Event block name
Event names
CLP1
LoadNormal ON
CLP1
LoadNormal OFF
CLP1
Overcurrent ON
CLP1
Overcurrent OFF
CLP1
CLPUActivated ON
CLP1
CLPUActivated OFF
CLP1
Block ON
CLP1
Block OFF
The function registers its operation into the last twelve (12) time-stamped registers. The register of the
function records the ON event process data for ACTIVATED, BLOCKED, etc. The table below
presents the structure of the function's register content.
Table. 5.4.3 - 240. Register content.
Date
and time
Event
L1/L2/L3
current
Time to
CLPUact
CLPU active time
Start-up
time
Releasing
time of
CLPU
Used SG
dd.mm.yyyy
hh:mm:ss.mss
Event
name
Phase
currents on
trigger time
Time remaining
before the
function is active
The time the
function has been
active before starting
Recorded
starting
time
Reclaim
time
counter
Setting
group
1...8
active
5.4.4 Switch-on-to-fault (SOTF)
The switch-on-to-fault (SOTF) function is used for speeding up the tripping when the breaker is closed
towards a fault or forgotten earthing to reduce the damage in the fault location. The function can be
used to control protection functions, or it can be used to directly trip a breaker if any of the connected
protection functions starts during the set SOTF time. The operation of the function is instant after the
conditions are met and any one signal connected to the "
Function input" input activates.
The inputs of the function are the following:
• initiating
• blocking
• setting group selection
• function trigger inputs.
The function can be initiated by a digital input, or by a circuit breaker "Close" command connected to
the "
SOTF activate input" input. The duration of the SOTF-armed condition can be set by the "Release
time for SOTF" setting parameter; it can be changed if the application so requires through setting group
selection.
The outputs of the function are BLOCKED, ACTIVE and TRIP signals. Additionally, the function outputs
the corresponding events and registers when any of these mentioned signals activate.
The following figure presents a simplified function block diagram of the switch-on-to-fault function.
A
AQ
Q-C255
-C255
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00035
291