![Arcteq AQ-C255 Скачать руководство пользователя страница 258](http://html1.mh-extra.com/html/arcteq/aq-c255/aq-c255_instruction-manual_2964905258.webp)
Mode
Description
4: Mag1 AND Mag2 AND
Mag3
All of the signals need to fulfill the pick-up condition. Each signal has their own pick-up
setting.
5: (Mag1 OR Mag2) AND
Mag3
Signals 1 OR 2 AND 3 need to fulfill the pick-up condition. Each signal has their own pick-up
setting.
The image below is an example of setting an analog comparison with three signals. The stage will trip if
Signal 1 or Signal 2 as well as Signal 3 fulfill the pick-up condition.
The settings for different comparisons are in the setting groups. This means that each signal parameter
can be changed by changing the setting group.
A
AQ
Q-C255
-C255
Instruction manual
Version: 2.06
256
© Arcteq Relays Ltd
IM00035
Содержание AQ-C255
Страница 1: ...AQ C255 Capacitor bank protection IED Instruction manual ...
Страница 2: ......
Страница 363: ...Figure 7 4 180 Example block scheme A AQ Q C255 C255 Instruction manual Version 2 06 Arcteq Relays Ltd IM00035 361 ...
Страница 384: ...Figure 8 14 202 Device installation A AQ Q C255 C255 Instruction manual Version 2 06 382 Arcteq Relays Ltd IM00035 ...