Figure. 5.3.6 - 48. Angle tracking of I0dir> function (Petersen coil earthed network model).
When the Petersen coil earthed (compensated) network mode is chosen, the device expects the fault
current to be in the opposite direction to the zero sequence voltage. Healthy phases of both
healthy and faulty feeders produce a capacitive current similar to the unearthed network. The
inductance of the Petersen coil compensates the capacitive current and therefore the residual current
in a fault location is close to zero. The size of the inductance is chosen according to the prospective
earth fault current of the network. The desired compensation grade is achieved when the K factor is
close to 1.0 and the network is fully compensated. The network is overcompensated when the K factor
is greater than 1.0, and undercompensated when the K factor is smaller than 1.0.