![Arcteq AQ-C255 Скачать руководство пользователя страница 193](http://html1.mh-extra.com/html/arcteq/aq-c255/aq-c255_instruction-manual_2964905193.webp)
If the blocking signal is active when the pick-up element activates, a BLOCKED signal is generated and
the function does not process the situation further. If the START function has been activated before the
blocking signal, it resets and the release time characteristics are processed similarly to when the pick-
up signal is reset.
The blocking of the function causes an HMI display event and a time-stamped blocking event with
information of the startup frequency values.
The blocking signal can also be tested in the commissioning phase by a software switch signal when
the relay's testing mode "Enable stage forcing" is activated (
General
→
Device).
The variables the user can set are binary signals from the system. The blocking signal needs to reach
the device minimum of 5 ms before the set operating delay has passed in order for the blocking to
activate in time.
Events and registers
The frequency function (abbreviated "FRQV" in event block names) generates events and registers
from the status changes in START, TRIP and BLOCKED. The user can select which event messages
are stored in the main event buffer: ON, OFF, or both.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.3.16 - 166. Event messages.
Event block name
Event names
FRQV1
f> Start ON
FRQV1
f> Start OFF
FRQV1
f> Trip ON
FRQV1
f> Trip OFF
FRQV1
f>> Start ON
FRQV1
f>> Start OFF
FRQV1
f>> Trip ON
FRQV1
f>> Trip OFF
FRQV1
f>>> Start ON
FRQV1
f>>> Start OFF
FRQV1
f>>> Trip ON
FRQV1
f>>> Trip OFF
FRQV1
f>>>> Start ON
FRQV1
f>>>> Start OFF
FRQV1
f>>>> Trip ON
FRQV1
f>>>> Trip OFF
FRQV1
f< Start ON
FRQV1
f< Start OFF
FRQV1
f< Trip ON
FRQV1
f< Trip OFF
FRQV1
f<< Start ON
FRQV1
f<< Start OFF
A
AQ
Q-C255
-C255
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00035
191
Содержание AQ-C255
Страница 1: ...AQ C255 Capacitor bank protection IED Instruction manual ...
Страница 2: ......
Страница 363: ...Figure 7 4 180 Example block scheme A AQ Q C255 C255 Instruction manual Version 2 06 Arcteq Relays Ltd IM00035 361 ...
Страница 384: ...Figure 8 14 202 Device installation A AQ Q C255 C255 Instruction manual Version 2 06 382 Arcteq Relays Ltd IM00035 ...