Name
Range
Step
Default
Description
Definite
operating
time delay
for alarm,
side 2
0…1800.000s
0.005s
5.000s
Defines the definite time delay for side 2 between the pick-up terms
being met and issuing an alarm signal.
Please note that this setting requires that the "Capacitor bank
configuration" parameter is set to "1: Bank size differs".
Pick-up
setting I
set
trip
0.10…50.00×In 0.01×In 0.2×In
Defines the pick-up threshold for the trip signal. Monitors the
unbalance current value.
Pick-up
setting for
fuse
operations
trip
1…50 fuses
1 fuse
5 fuses
Defines the pick-up threshold per side for counted fuse operations.
Please note that this setting requires that the "Count fuse operations
per side for action" parameter is set to "1: Yes, fuses or current".
Pick-up
setting Iset
trip, side 2
0.10…50.00×In 0.01×In 0.2×In
Defines the pick-up threshold for the trip signal for side 2. Monitors the
unbalance current value.
Please note that this setting requires that the "Capacitor bank
configuration" parameter is set to "1: Bank size differs".
Pick-up
setting for
fuse
operations
trip, side 2
1…50 fuses
1 fuse
5 fuses
Defines the pick-up threshold per side for counted fuse operations for
side 2.
Please note that this setting requires that the "Count fuse operations
per side for action" parameter is set to "1: Yes, fuses or current" as well
as that the "Capacitor bank configuration" parameter is set to "1: Bank
size differs".
The pick-up activation of the function is not directly equal to the START signal generation of the
function. The START signal is allowed if the blocking condition is not active.
Read-only parameters
The relay's
Info page displays useful, real-time information on the state of the protection function. It is
accessed either through the relay's HMI display, or through the setting tool software when it is
connected to the relay and its Live Edit mode is active.
Table. 5.3.2.2 - 56. Information displayed by the function.
Name
Range
Step
Description
CNU> (50UB)
LN behaviour
1: On
2: Blocked
3: Test
4: Test/Blocked
5: Off
-
Displays the mode of CNU block.
This parameter is visible only when
Allow setting of individual LN mode is
enabled in
General menu.
Measured
unbalance
current
0.00...50.00 A
0.01 A Unbalance current in amperes.
Unbalance
current angle
-360.00...360.00 deg
0.01
deg
Unbalance current angle.
CNU> (50UB)
condition
0: Normal
1: Start
2: Trip
3: Blocked
-
Displays status of the protection function.
Expected
Alarm time
-1800.000...1800.000s 0.005s
Displays the expected time to alarm when a fault occurs. When IDMT
mode is used, the expected operating time depends on the current
unbalance value. If the measured current changes during a fault, the
expected operating time changes accordingly.
Time remaining
to Alarm
0.000...1800.000s
0.005s When the function has detected a fault and counts down time towards an
alarm, this displays how much time is left before tripping occurs.
A
AQ
Q-C255
-C255
Instruction manual
Version: 2.06
72
© Arcteq Relays Ltd
IM00035
Содержание AQ-C255
Страница 1: ...AQ C255 Capacitor bank protection IED Instruction manual ...
Страница 2: ......
Страница 363: ...Figure 7 4 180 Example block scheme A AQ Q C255 C255 Instruction manual Version 2 06 Arcteq Relays Ltd IM00035 361 ...
Страница 384: ...Figure 8 14 202 Device installation A AQ Q C255 C255 Instruction manual Version 2 06 382 Arcteq Relays Ltd IM00035 ...