The inductance connected to the star point of an incoming transformer or -as in most cases- to a
earthing transformer compensates the capacitance of the network; however, this prevents the
capacitive fault current to be measured. The fault detection is handled by connecting the resistance in
parallel with the inductance. This resistance includes the amplitude of the fault current. In
undercompensated or overcompensated situations the resistive component does not change during
the fault; therefore, selective tripping is ensured even when the network is slightly undercompensated
or overcompensated.
Directly earthed or small impedance network (67N)
Figure. 5.3.6 - 49. Angle tracking of I0dir> function (directly earthed or small impedance network).
In a directly earthed network the amplitude of a single-phase fault current is similar to the amplitude of
a short-circuit current. Directly earthed or small impedance network schemes are normal in
transmission, distribution and industry.
A
AQ
Q-C255
-C255
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00035
105